Properties of moist air

Treat moist air as dry air plus water vapour, both ideal gases at a common temperature and volume. A psychrometric state requires the total pressure and two independent properties. Keep the dry-air basis throughout every property and process balance.

4.1 Humidity measures

Past papers · ME 2020–2026 (10 papers): 2 questions, 3 marks

Let pp be total pressure, pvp_v water-vapour partial pressure and pa=p−pvp_a=p-p_v dry-air partial pressure. Let pws(T)p_{ws}(T) be pure-water saturation pressure at the dry-bulb temperature. The model below is suitable for ordinary atmospheric-pressure air conditioning without suspended droplets.

At constant total pressure and fixed ω\omega, sensible heating keeps pvp_v fixed while pwsp_{ws} rises, so relative humidity falls. In a sealed rigid container, pvp_v changes with temperature; the constant-pressure shortcut does not apply.

4.2 Enthalpy, volume and density

For the approximate property model, take the enthalpies of liquid water and dry air as zero at 0°C. Write TCT_C for dry-bulb temperature in °C and T=TC+273.15T=T_C+273.15 K. The heat-capacity constants are approximations, not exact universal properties; question-supplied values take precedence.

4.3 Dry bulb, wet bulb and dew point

Dry-bulb temperature is the air temperature. Dew point is the temperature at which constant-pressure cooling first reaches saturation without changing humidity ratio. A ventilated wet bulb cools by evaporation; its reading approximates thermodynamic wet-bulb temperature for ordinary air–water mixtures, with appropriate ventilation and negligible radiation error.

For ordinary unsaturated air above freezing, Tdp<Twb<TdbT_{\rm dp}<T_{\rm wb}<T_{\rm db}; at saturation all three coincide. The difference Tdb−TwbT_{\rm db}-T_{\rm wb} is wet-bulb depression; Tdb−TdpT_{\rm db}-T_{\rm dp} is dew-point depression. Below freezing distinguish frost point, ice bulb and liquid-water references rather than extending the liquid-water formula blindly.

4.4 Reading the psychrometric chart

Past papers · ME 2020–2026 (10 papers): 1 question, 1 mark

Use the chart for the stated total pressure. On the usual dry-bulb/humidity-ratio presentation, locate the state using two independent properties, then read the others. Dry-bulb temperature runs to the right and humidity ratio upward; the saturation boundary limits droplet-free states.

Family or constructionWhat to read
Constant dry-bulb temperatureVertical line on an orthogonal TCT_C–ω\omega sketch
Constant humidity ratioHorizontal line; dew point lies at its saturation intersection
Relative-humidity curvesCurves between dry air and the 100% saturation boundary
Constant enthalpyDownward-sloping lines on a TCT_C–ω\omega sketch
Constant wet-bulb temperatureClose to, but not identical to, constant-enthalpy lines
Constant specific volumeSloping lines, usually steeper than constant-enthalpy lines
Adiabatic mixingExact straight lever rule in hh–ω\omega coordinates; nearly straight in TCT_C–ω\omega

Psychrometric process directions on an original qualitative sketch. This is not a property chart for numerical readings.Psychrometric process directions on an original qualitative sketch. This is not a property chart for numerical readings.

A commercial chart may use oblique enthalpy coordinates; follow its printed grid instead of judging angles by eye. A point above the saturation curve implies fog or condensation and cannot be handled as unsaturated ideal moist air alone. Do not extrapolate a chart to a different altitude pressure.

Last-minute recall

  • Humidity ratio uses dry-air mass; vapour mass fraction uses total moist-air mass.
  • ϕ=pv/pws\phi=p_v/p_{ws}; dew point satisfies pws(Tdp)=pvp_{ws}(T_{\rm dp})=p_v.
  • The dry-air partial pressure is p−pvp-p_v.
  • Enthalpy uses °C relative to the stated zero; gas volume uses K.
  • Chart enthalpy and volume are per kg dry air.
  • Wet-bulb and constant-enthalpy lines are close, not identical.
  • A pressure and two independent properties fix a moist-air state.