Air-conditioning processes
A steady air-conditioning calculation conserves dry air, water and energy. Establish inlet and outlet states, then multiply the specific changes by dry-air flow. Cooling coils, humidifiers and mixers differ chiefly in where water enters or leaves the boundary.
5.1 Sensible heating and cooling
A sensible process changes dry-bulb temperature at constant humidity ratio. Cooling stays purely sensible only while the surface and air conditions do not cause condensation; a surface below the incoming dew point can remove moisture.
Sensible heating lowers relative humidity but leaves dew point unchanged at fixed pressure; sensible cooling does the reverse until saturation. Reheating dehumidified air raises its dry bulb without restoring the removed water.
5.2 Humidification and evaporative cooling
For injection with no liquid drainage, all added water leaves as vapour. An air washer approaches a saturated state depending on water temperature and contact effectiveness. Steam injection commonly raises enthalpy; its temperature effect follows the balance rather than a universal direction rule.
For an adiabatic liquid-water humidifier, use liquid ; for steam injection use steam . If water enters and drains in different amounts or at different temperatures, include both liquid streams in the balance. The constant-enthalpy approximation neglects their net enthalpy contribution.
5.3 Cooling with dehumidification
Past papers · ME 2020–2026 (10 papers): 1 question, 2 marks
Condensation removes water as well as heat. Use a cooling coil with dry-air inlet 1, outlet 2 and liquid condensate leaving at a specified temperature. Positive cooling load means heat removed from the air and condensate control volume.
5.4 Apparatus dew point and bypass factor
The apparatus dew point (ADP) is the effective saturated surface state obtained by extending the cooling/dehumidification process toward saturation. Model the outlet as a mixture of air that bypasses the coil and air that reaches ADP. Bypass fraction is on a dry-air mass basis.
For a sensible heating coil, replace ADP by the effective coil surface temperature and use the temperature ratio. BF = 0 means complete approach to the surface state; BF = 1 means no treatment. A requested ADP must lie on the saturation curve at the chart pressure.
5.5 Mixing two moist-air streams
Streams must meet at a common pressure. For an insulated mixer with no work, no liquid injection and no condensation, dry-air flow weights both enthalpy and humidity ratio. Volume-flow weighting is generally incorrect.
5.6 Room loads and supply-air quantity
For a steady room, supply air at state absorbs the sensible and latent loads and leaves at room state . The return/outdoor-air mixer and the cooling coil have their own balances; room load and coil load differ when ventilation or other equipment adds heat.
At SHF = 1, the load is purely sensible and the room process is horizontal on a – sketch. At SHF approaching zero, the slope expression is unsuitable because the dry-bulb difference tends to zero. For a nonstandard source, write total enthalpy balance instead of forcing the sensible/latent split.
Last-minute recall
- Air processes conserve dry air even while water is added or removed.
- Sensible heating and cooling keep humidity ratio fixed.
- Evaporative cooling raises humidity and approaches the inlet wet bulb under the stated idealisation.
- Dehumidification rate is dry-air flow times the drop in humidity ratio.
- Subtract outgoing condensate enthalpy in an exact cooling-coil load.
- BF is the untreated fraction; CF is one minus BF.
- Mix using dry-air mass and enthalpy, then recover temperature.
- Room sensible heat factor sets the room process direction; ventilation changes the coil load.