Refrigeration and heat pumps
A refrigerator is rated by heat removed from the cold region; a heat pump is rated by heat delivered to the warm region. Use the same system boundary when comparing their coefficients of performance. Fluid enthalpies and component balances are usually the quickest route to a numerical answer.
3.1 COP, limits and capacity units
Past papers · ME 2020–2026 (10 papers): 1 question, 2 marks
Let be heat absorbed from the cold reservoir, heat delivered to the hot reservoir, and net work supplied, all positive magnitudes. A cyclic work-driven device satisfies .
3.2 Simple vapour-compression cycle
Past papers · ME 2020–2026 (10 papers): 2 questions, 3 marks
Use 1 at compressor inlet, 2 at compressor outlet, 3 at condenser exit, and 4 after the expansion valve. In the standard ideal cycle, 1 is saturated vapour, 3 saturated liquid, 1–2 is isentropic, and the heat exchangers have no pressure drop. Expansion 3–4 is throttling, not isentropic expansion.
| Process | On a pressure–enthalpy chart | Useful state relation |
|---|---|---|
| Compression 1–2 | Pressure and enthalpy rise | only for the ideal compressor |
| Condensation 2–3 | Constant-pressure line toward lower enthalpy | Includes desuperheating before condensation |
| Valve 3–4 | Constant-enthalpy line toward lower pressure | Usually generates flash vapour |
| Evaporation 4–1 | Constant-pressure line toward higher enthalpy | Two-phase part is also isothermal for a pure fluid |
Schematic vapour-compression path on pressure–enthalpy axes; the dome and state positions are qualitative.
3.3 Actual compression and suction volume
Locate the isentropic discharge state at the same discharge pressure as the actual state. Compressor mechanical and motor efficiencies describe additional losses and are not interchangeable with isentropic efficiency.
Suction-line pressure drop increases the pressure ratio and can reduce capacity. Lower evaporator pressure generally reduces COP and volumetric capacity; higher condenser pressure generally reduces COP. Use actual properties for quantitative comparisons. Compressor clearance and machine performance correlations: see the Turbomachinery handbook.
3.4 Subcooling and superheating
Liquid subcooling lowers the valve-inlet enthalpy. Useful evaporator superheat and unwanted suction-line superheat have different load boundaries: only heat absorbed inside the refrigerated space counts as useful refrigeration.
3.5 Multiple evaporators and cascade cycles
Do not average COPs by refrigerant mass. Add useful cooling rates and actual work rates. At a common suction pressure, streams mix by mass-weighted enthalpy; an evaporator at a higher pressure needs pressure reduction before that mixer.
A flash separator at an intermediate pressure is another mass/enthalpy mixer–splitter: evaluate the inlet flash quality from , then split vapour and liquid at that pressure. More elaborate staged systems follow the same balances; no universal optimum intermediate pressure applies to all refrigerants and intercooling arrangements.
3.6 Heat-driven vapour absorption
Absorption replaces vapour compression with an absorber, solution pump and generator. The absorber takes up refrigerant vapour at low pressure and rejects heat; the pump raises solution pressure; generator heat releases high-pressure refrigerant. The condenser, valve and evaporator retain their refrigeration roles.
| Pair | Refrigerant | Absorbent | Consequence |
|---|---|---|---|
| Ammonia–water | Ammonia | Water | Water vapour carried from the generator must be reduced by rectification |
| Water–lithium bromide | Water | Lithium bromide solution | Water freezes at 0°C, so the evaporator must stay above 0°C |
For an adiabatic generator material balance, conserve total solution mass and refrigerant mass separately. “Strong solution” is ambiguous unless it states which constituent is concentrated; use explicit mass fractions instead.
3.7 Gas refrigeration
In the reversed Brayton or Bell–Coleman cycle, 1–2 is compression, 2–3 high-pressure cooling, 3–4 expansion in a turbine and 4–1 low-pressure heat absorption. The working fluid remains a gas. This refrigeration cycle is separate from the power Brayton cycle in the Thermodynamics handbook.
3.8 Refrigerant properties in cycle problems
Use the refrigerant named in the question and its supplied saturation/superheat data. Water, ammonia and fluorocarbon refrigerants have very different pressure scales; there is no transferable table of enthalpies. Larger latent heat alone does not establish a larger COP: compressor work and valve-inlet enthalpy also matter.
| Property or feature | How it enters the calculation |
|---|---|
| Saturation pressures | Determine compressor pressure ratio at specified evaporation and condensation temperatures |
| Suction specific volume | Converts refrigerant mass flow to compressor volume flow |
| Liquid enthalpy before throttling | Fixes valve-outlet enthalpy and flash vapour |
| Superheated entropy/enthalpy data | Determine isentropic compressor discharge |
| Critical temperature | Ordinary condensation requires operation below the critical temperature |
| Zeotropic mixture temperature glide | Constant pressure need not mean constant temperature during phase change |
Refrigerant safety classifications and current environmental restrictions are not cycle formulas and are not needed for the cycle calculations here. Do not infer a refrigerant's suitability from COP alone.
Last-minute recall
- COP uses useful heat divided by the relevant energy input.
- A throttle preserves enthalpy; an ideal compressor preserves entropy.
- Flash vapour reduces the liquid available to evaporate in the cold space.
- Compressor efficiency increases actual work above the isentropic value.
- Subcooling increases refrigeration effect at unchanged suction conditions.
- Suction-line heat outside the cold space is not useful cooling.
- Cascade stages exchange equal heat rates, not equal refrigerant mass rates.
- Absorption uses generator heat; its reversible bound needs three temperatures.
- Bell–Coleman COP subtracts recovered expander work from compressor work.