Chapter 3

Refrigeration and heat pumps

A refrigerator is rated by heat removed from the cold region; a heat pump is rated by heat delivered to the warm region. Use the same system boundary when comparing their coefficients of performance. Fluid enthalpies and component balances are usually the quickest route to a numerical answer.

3.1 COP, limits and capacity units

Past papers · ME 2020–2026 (10 papers): 1 question, 2 marks

Let QLQ_L be heat absorbed from the cold reservoir, QHQ_H heat delivered to the hot reservoir, and WinW_{\rm in} net work supplied, all positive magnitudes. A cyclic work-driven device satisfies QH=QL+WinQ_H=Q_L+W_{\rm in}.

3.2 Simple vapour-compression cycle

Past papers · ME 2020–2026 (10 papers): 2 questions, 3 marks

Use 1 at compressor inlet, 2 at compressor outlet, 3 at condenser exit, and 4 after the expansion valve. In the standard ideal cycle, 1 is saturated vapour, 3 saturated liquid, 1–2 is isentropic, and the heat exchangers have no pressure drop. Expansion 3–4 is throttling, not isentropic expansion.

ProcessOn a pressure–enthalpy chartUseful state relation
Compression 1–2Pressure and enthalpy rises2s=s1s_{2s}=s_1 only for the ideal compressor
Condensation 2–3Constant-pressure line toward lower enthalpyIncludes desuperheating before condensation
Valve 3–4Constant-enthalpy line toward lower pressureUsually generates flash vapour
Evaporation 4–1Constant-pressure line toward higher enthalpyTwo-phase part is also isothermal for a pure fluid

Schematic vapour-compression path on pressure–enthalpy axes; the dome and state positions are qualitative.Schematic vapour-compression path on pressure–enthalpy axes; the dome and state positions are qualitative.

3.3 Actual compression and suction volume

Locate the isentropic discharge state at the same discharge pressure as the actual state. Compressor mechanical and motor efficiencies describe additional losses and are not interchangeable with isentropic efficiency.

Suction-line pressure drop increases the pressure ratio and can reduce capacity. Lower evaporator pressure generally reduces COP and volumetric capacity; higher condenser pressure generally reduces COP. Use actual properties for quantitative comparisons. Compressor clearance and machine performance correlations: see the Turbomachinery handbook.

3.4 Subcooling and superheating

Liquid subcooling lowers the valve-inlet enthalpy. Useful evaporator superheat and unwanted suction-line superheat have different load boundaries: only heat absorbed inside the refrigerated space counts as useful refrigeration.

3.5 Multiple evaporators and cascade cycles

Do not average COPs by refrigerant mass. Add useful cooling rates and actual work rates. At a common suction pressure, streams mix by mass-weighted enthalpy; an evaporator at a higher pressure needs pressure reduction before that mixer.

A flash separator at an intermediate pressure is another mass/enthalpy mixer–splitter: evaluate the inlet flash quality from (hin−hf)/hfg(h_{\rm in}-h_f)/h_{fg}, then split vapour and liquid at that pressure. More elaborate staged systems follow the same balances; no universal optimum intermediate pressure applies to all refrigerants and intercooling arrangements.

3.6 Heat-driven vapour absorption

Absorption replaces vapour compression with an absorber, solution pump and generator. The absorber takes up refrigerant vapour at low pressure and rejects heat; the pump raises solution pressure; generator heat releases high-pressure refrigerant. The condenser, valve and evaporator retain their refrigeration roles.

PairRefrigerantAbsorbentConsequence
Ammonia–waterAmmoniaWaterWater vapour carried from the generator must be reduced by rectification
Water–lithium bromideWaterLithium bromide solutionWater freezes at 0°C, so the evaporator must stay above 0°C

For an adiabatic generator material balance, conserve total solution mass and refrigerant mass separately. “Strong solution” is ambiguous unless it states which constituent is concentrated; use explicit mass fractions instead.

3.7 Gas refrigeration

In the reversed Brayton or Bell–Coleman cycle, 1–2 is compression, 2–3 high-pressure cooling, 3–4 expansion in a turbine and 4–1 low-pressure heat absorption. The working fluid remains a gas. This refrigeration cycle is separate from the power Brayton cycle in the Thermodynamics handbook.

3.8 Refrigerant properties in cycle problems

Use the refrigerant named in the question and its supplied saturation/superheat data. Water, ammonia and fluorocarbon refrigerants have very different pressure scales; there is no transferable table of enthalpies. Larger latent heat alone does not establish a larger COP: compressor work and valve-inlet enthalpy also matter.

Property or featureHow it enters the calculation
Saturation pressuresDetermine compressor pressure ratio at specified evaporation and condensation temperatures
Suction specific volumeConverts refrigerant mass flow to compressor volume flow
Liquid enthalpy before throttlingFixes valve-outlet enthalpy and flash vapour
Superheated entropy/enthalpy dataDetermine isentropic compressor discharge
Critical temperatureOrdinary condensation requires operation below the critical temperature
Zeotropic mixture temperature glideConstant pressure need not mean constant temperature during phase change

Refrigerant safety classifications and current environmental restrictions are not cycle formulas and are not needed for the cycle calculations here. Do not infer a refrigerant's suitability from COP alone.

Last-minute recall

  • COP uses useful heat divided by the relevant energy input.
  • A throttle preserves enthalpy; an ideal compressor preserves entropy.
  • Flash vapour reduces the liquid available to evaporate in the cold space.
  • Compressor efficiency increases actual work above the isentropic value.
  • Subcooling increases refrigeration effect at unchanged suction conditions.
  • Suction-line heat outside the cold space is not useful cooling.
  • Cascade stages exchange equal heat rates, not equal refrigerant mass rates.
  • Absorption uses generator heat; its reversible bound needs three temperatures.
  • Bell–Coleman COP subtracts recovered expander work from compressor work.