Symmetrical components and faults
A balanced network separates into positive-, negative- and zero-sequence circuits. An unbalanced fault couples those circuits through its boundary conditions. Select the faulted phases first, then reconstruct phase currents and voltages.
8.1 Component transformation
Past papers · EE 2020–2026 (7 papers): 3 questions, 5 marks
Use phase order and . The sequence components below refer to phase a, in the order zero, positive, negative.
Line-to-line voltages contain no zero sequence because equal components cancel on subtraction. A common phase rotation multiplies every sequence phasor by the same rotation and leaves sequence magnitudes unchanged.
8.2 Sequence impedances and transformer paths
Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark
A synchronous generator has an emf only in its positive-sequence network. Its positive-sequence reactance depends on the time frame; negative and zero sequence use the given machine data.
| Connection | Zero-sequence line-current path |
|---|---|
| Ungrounded star | Blocked when neutral has no return path |
| Delta terminals | No external zero-sequence line current; internal circulating current can exist |
| Grounded star–delta transformer | Grounded-star side has a path through transformer leakage and delta circulation |
| Grounded star–grounded star | Can transfer zero sequence; include both grounding impedances and the stated magnetic model |
| Grounded star–ungrounded star | Do not assume a leakage-only path; magnetising/core path may matter |
For an ordinary transposed overhead line, ; the earth-return path generally makes different and often larger in magnitude. Use given data rather than imposing a fixed ratio.
Positive and negative sequence experience opposite phase shifts across a phase-shifting transformer. Use the specified vector group and voltage reference; there is no universal “always +30°” rule. Use the given zero-sequence model for core-dependent cases.
8.3 Balanced three-phase faults
Past papers · EE 2020–2026 (7 papers): 2 questions, 3 marks
With balanced prefault conditions, a symmetrical three-phase fault excites only positive sequence. During the initial cycles use subtransient reactance if requested; later stages use transient or synchronous reactance.
For pu and a bolted fault through reactance , fault level is . Do not use depressed fault-point voltage to quote the conventional rated-voltage fault MVA.
Do not reuse the steady-state emf behind synchronous reactance with subtransient reactance. Reconstruct the internal emf from the prefault terminal voltage and current first. For an unloaded generator with negligible resistance, both internal emfs equal the terminal voltage.
For very high , the worst first peak approaches twice the symmetrical peak, . This is a limiting waveform result, not a universal breaker rating multiplier.
8.4 Single line to ground
Fault phase a to earth through , with currents into the fault. Let be prefault positive-sequence phase-a voltage at the fault point and the sequence Thevenin impedances seen there.
The three sequence networks connect in series. If , current tends to zero in this model; real capacitive earth-return paths may still carry current if retained in the network.
8.5 Line to line
Past papers · EE 2020–2026 (7 papers): 1 question, 2 marks
Fault phases b and c through an impedance between them, with phase a unfaulted. is not an impedance from the joined phases to ground.
For a bolted fault with , its phase-current magnitude is times the three-phase bolted-fault current for the same . Compare phase currents, not sequence currents.
8.6 Double line to ground
Phases b and c are joined together, then connected through a common to ground. Separate arc impedances in each phase form a different circuit.
Here positive sequence feeds negative sequence in parallel with the zero-sequence path including . As the ground path opens, the result tends to the b–c line-to-line fault.
8.7 Reconstructing postfault quantities
Sequence diagrams solve the fault coupling; the original phase quantities still determine conductor current, insulation stress and relay measurements.
Reconstruct and verify the fault boundary conditions. For unbalanced systems use , not a balanced shortcut. A single-line-ground fault is not always smaller than a three-phase fault: the sequence impedances decide.
Last-minute recall
- State phase order and sequence order before multiplying a matrix.
- Zero sequence disappears from line-to-line voltage.
- Neutral impedance enters the zero-sequence network as .
- Delta terminals block zero-sequence line current but allow internal circulation.
- Three-phase fault: positive sequence only.
- Single-line-ground: all three sequence currents equal.
- Line-line: zero sequence absent and positive equals minus negative sequence.
- Double-line-ground: reconstruct both faulted phase currents and their sum.