Voltage and frequency control
Real-power imbalance changes rotor speed and frequency. Reactive-power imbalance strongly affects voltage in predominantly inductive networks. These couplings are useful approximations, not exact separation in every network.
7.1 Primary frequency response
Past papers · EE 2020–2026 (7 papers): 2 questions, 3 marks
A governor's droop sets how much generation increases when frequency falls. Inertia determines the initial rate of frequency change; droop and frequency-sensitive load determine the settled primary response.
A droop of pu frequency per pu power on rating gives Hz/MW. The same percentage droop on unequal ratings does not give equal MW/Hz response. With fixed references and , incremental sharing is proportional to . Total outputs have that ratio only when the no-load frequency references coincide; otherwise include the initial outputs or setpoints.
7.2 Frequency dynamics and secondary control
Past papers · EE 2020–2026 (7 papers): 1 question, 2 marks
A primary governor reduces the error but usually leaves a frequency offset. Integral secondary control adjusts the reference to restore frequency and scheduled net interchange.
For tie-line , its linearised change is with . Electrical angle changes satisfy .
7.3 Excitation and voltage regulation
An automatic voltage regulator compares measured terminal voltage with its reference and changes excitation. Higher excitation usually increases reactive export into a stiff grid. Tap changers and shunt devices also regulate voltage but have different response times and limits.
In a synchronised interconnected system, AGC changes mechanical-power references to regulate the common frequency and area interchange. AVR changes field excitation; its strongest voltage effect is near the controlled generator, although network coupling remains.
Voltage stability concerns whether the network can maintain acceptable bus voltages as load and reactive demand change; reactive limits can remove an otherwise feasible operating point. Frequency stability concerns recovery of generation–load balance and frequency after a major imbalance.
A first-order block, if specified, has with gain and time constant . Increasing gain can improve steady regulation while reducing dynamic margin. Reactive limits and saturation invalidate an unlimited linear controller model.
Last-minute recall
- A positive load increment initially lowers frequency.
- Convert percentage droop to the same MW base before sharing load.
- Primary control normally leaves a frequency offset.
- Integral secondary control restores the reference and scheduled interchange.
- Inertia sets rate of change, not the settled primary frequency error.
- Excitation controls reactive exchange and voltage within equipment limits.