Chapter 9

Protection and circuit breakers

A relay decides whether to trip; a circuit breaker interrupts the current. Protection must distinguish internal faults from load and external faults, then isolate the smallest practical part of the network with backup available.

9.1 Overcurrent protection and coordination

Overcurrent protection compares measured current with pickup. Time grading makes upstream protection slower than downstream protection for the same fault. Directional supervision is needed when fault current can arrive from multiple sources.

Instantaneous overcurrent has no intentional delay. Definite-time overcurrent has a fixed intentional delay above pickup. Inverse-time protection gets faster as fault current rises. Use the exact curve and constants supplied in the question; curves with the same informal name need not share numerical settings.

A CT secondary should not be opened while its primary carries current. CT saturation can distort measured current and affect both overcurrent and differential protection.

9.2 Directional and differential principles

Past papers · EE 2020–2026 (7 papers): 2 questions, 3 marks

A directional element compares current with a polarising voltage or another reference. It cannot infer direction from current magnitude alone.

If both CT arrows point into the protected zone, use ∣I1+I2∣|I_1+I_2| instead. Bias restrains operation during large through currents and CT mismatch. Transformer differential protection must compensate ratio, phase shift and zero-sequence effects; inrush restraint prevents magnetising inrush being treated as an internal fault.

For the displayed delta differences, positive-sequence output is multiplied by 3ejπ/6\sqrt3 e^{j\pi/6} and negative sequence by 3e−jπ/6\sqrt3 e^{-j\pi/6}, in addition to ktk_t. Zero sequence cancels. Actual winding dots and delta orientation decide the sign and which adjacent current is subtracted: trace the circuit before using a compensation matrix. Basic transformer ampere-turn balance: see the Electrical Machines handbook.

For directional placement, trace every possible source-to-fault current path. A healthy parallel feeder can backfeed a fault through the remote bus; a reverse-blocking directional element at that feeder’s remote end prevents its unnecessary trip. Combine this path test with time grading and primary/backup zones.

9.3 Distance characteristics

Past papers · EE 2020–2026 (7 papers): 3 questions, 4 marks

Distance elements estimate an apparent impedance from measured voltage and current. The R–X plane makes reach and direction easier to read. A plain impedance or reactance element is not inherently forward directional.

Typical applications: differential protection for internal generator/transformer faults and bus zones; directional overcurrent for networks with several supply paths; distance protection for transmission lines; offset-mho protection for generator loss of excitation. Equipment-specific backup and supervision are still required.

Zone 1 is set to underreach the remote end for security; delayed zones provide extended and backup reach. Exact percentage reaches are settings, not fixed physical constants. Resistance at the fault can cause underreach of impedance and mho elements; a reactance element is less sensitive to added resistance but needs directional supervision.

Ideal impedance, reactance and mho boundaries have different shapes and directional properties.Ideal impedance, reactance and mho boundaries have different shapes and directional properties.

9.4 Phase and ground measuring loops

A correctly chosen phase-phase loop removes zero sequence. A ground loop must compensate the different zero-sequence line impedance.

Some texts define compensation against I0I_0 rather than 3I03I_0; their coefficient is three times k0k_0. Do not mix that coefficient with residual current. Remote infeed, mutual zero-sequence coupling and fault resistance can change apparent reach.

9.5 Interruption and ratings

AC interruption uses a natural current zero followed by sufficient dielectric recovery. A DC breaker needs a means to force or commutate current to zero. Opening an isolator is not a substitute for fault interruption.

Making duty is a peak-current duty; breaking duty is usually specified with a symmetrical RMS component and DC-offset requirements. Apply any stated making factor only to its defined RMS reference. Continuous-current rating, short-time withstand and interrupting rating are separate requirements.

MediumInterruption feature
OilArc decomposes oil; gas and cooling assist deionisation
Air blastPressurised air cools and removes ionised gas
Sulphur hexafluorideElectronegative gas supports dielectric recovery
VacuumMetal-vapour arc extinguishes near current zero; rapid recovery

9.6 Recovery voltage and current chopping

Transient recovery voltage appears across separating contacts. Successful interruption requires recovering dielectric strength to stay above the applied recovery stress. The simple LC model is useful only over the short high-frequency transient.

The average rise to the first peak differs from the maximum instantaneous slope. For a resistor RdR_d across the contacts in the ideal source–LL feeding parallel Rd,CR_d,C model, the natural characteristic is s2+s/(RdC)+1/(LC)=0s^2+s/(R_dC)+1/(LC)=0. Critical damping occurs at Rd=12L/CR_d=\tfrac12\sqrt{L/C}; a smaller positive resistance gives an overdamped response. This is not the series-RLC critical resistance. Capacitive switching can leave trapped charge; compare voltage across the gap, not merely source voltage to earth.

Last-minute recall

  • Pickup multiple uses relay-secondary current and pickup on the same base.
  • Coordinate total clearing times with a stated margin.
  • Direction requires a polarising reference.
  • Differential currents need ratio, phase and direction compensation.
  • CT/VT scaling multiplies impedance by nCT/nVTn_{CT}/n_{VT}.
  • Mho passes through the origin; reactance is a horizontal boundary in R–X.
  • A peak making current and an RMS breaking current are different quantities.
  • Average RRRV is not the peak derivative of recovery voltage.