Chapter 10

Stability and the equal-area criterion

Rotor-angle stability concerns synchronism after a disturbance. Small-disturbance analysis linearises about an operating point; transient stability follows the large-angle motion. Voltage and frequency stability are distinct system limitations.

10.1 Power angle and equilibrium

Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark

For a classical round-rotor generator behind a constant internal emf, connected to an infinite bus through reactance, electrical output follows a sine curve. The infinite bus holds voltage and frequency fixed.

For 0<Pm<Pmax⁡0<P_m<P_{\max}, the lower-angle equilibrium δ0=sin⁡−1(Pm/Pmax⁡)\delta_0=\sin^{-1}(P_m/P_{\max}) has Kδ>0K_\delta>0; the upper one π−δ0\pi-\delta_0 has Kδ<0K_\delta<0. Positive synchronising stiffness alone gives undamped oscillations if damping is absent.

10.2 Swing equation and inertia

Past papers · EE 2020–2026 (7 papers): 1 question, 2 marks

A positive accelerating power means mechanical input exceeds electrical output. Rotor speed then rises above synchronous speed and the rotor angle increases.

Electrical and mechanical rotor angles satisfy δ=(p/2)θm\delta=(p/2)\theta_m up to the synchronous reference, so θ¨m=(2/p)δ¨\ddot\theta_m=(2/p)\ddot\delta for pp poles; multiply rad/s² by 180/π180/\pi for degree/s².

Aggregation assumes coherent rotor motion on a common frequency base. For two classical machines on the same power base, the relative-angle inertia parameter is H1H2/(H1+H2)H_1H_2/(H_1+H_2) after writing their relative swing equation; mechanical forcing must also be transformed. The infinite-bus limit recovers the finite machine's inertia.

10.3 Equal areas and critical clearing angle

Past papers · EE 2020–2026 (7 papers): 2 questions, 4 marks

Assume a classical single-machine infinite-bus model, negligible damping, constant mechanical input and piecewise fixed transfer curves. Let prefault, fault-on and postfault electrical powers be Ppresin⁡δP_{\rm pre}\sin\delta, Pfsin⁡δP_f\sin\delta and Ppsin⁡δP_p\sin\delta.

Available decelerating area must at least absorb accumulated acceleration. If the postfault transfer maximum is below mechanical input, there is no postfault equilibrium in this model. For clearing and reclosing sequences, integrate the correct curve over each angle interval; one fault curve cannot represent every switching stage.

For zero fault-on transfer and restoration of the prefault network, Pf=0P_f=0, Pp=Ppre=Pmax⁡P_p=P_{\rm pre}=P_{\max}, giving cos⁡δc=(Pm/Pmax⁡)(π−2δ0)−cos⁡δ0\cos\delta_c=(P_m/P_{\max})(\pi-2\delta_0)-\cos\delta_0. Reject an inverse-cosine result outside the physically admissible interval rather than forcing a numerical answer.

The accelerating area must be recovered by decelerating area before the unstable equilibrium.The accelerating area must be recovered by decelerating area before the unstable equilibrium.

10.4 Clearing time and energy interpretation

Angle at clearing is not the maximum swing angle. Immediately after clearing, electrical output may exceed mechanical input while the rotor remains faster than synchronous speed, so angle continues to increase.

For a nonzero sine-shaped fault-on transfer, acceleration is not constant. Integrate the swing equation to obtain clearing time. In the classical equal-area model, inertia affects time but not the critical clearing angle. Faster clearing, lower transfer reactance and larger postfault transfer capability can improve first-swing margin.

Last-minute recall

  • A stable lower-angle equilibrium needs positive synchronising stiffness.
  • Damping decides whether small oscillations decay.
  • Use electrical radians throughout swing and area calculations.
  • Mechanical input is approximately constant over the first swing.
  • Clearing angle and maximum rotor angle are different.
  • Use the postfault curve to calculate available deceleration.
  • Inertia changes critical clearing time, not the classical critical angle.
  • The constant-acceleration time formula requires zero fault-on transfer.