Chapter 5

Line-current harmonics and power factor

Always identify the source-voltage reference before assigning harmonic phase. Harmonic amplitudes determine heating; only matching voltage and current harmonics contribute to average active power.

5.1 Harmonic convention and power definitions

Past papers · EE 2020–2026 (7 papers): 2 questions, 2 marks

Write a current using signed sine and cosine coefficients relative to θ=ωt\theta=\omega t: is=I0+∑h≥1[ahcos⁡(hθ)+bhsin⁡(hθ)]i_s=I_0+\sum_{h\ge1}[a_h\cos(h\theta)+b_h\sin(h\theta)]. Here I0I_0 is DC current, hh harmonic order and ah,bha_h,b_h are peak coefficients (A). A positive ϕh\phi_h in I^hsin⁡(hθ−ϕh)\hat I_h\sin(h\theta-\phi_h) denotes lag relative to sin⁡(hθ)\sin(h\theta), with I^h≥0\hat I_h\ge0.

Use kdk_d for distortion factor and DPF for displacement factor; the abbreviation DF is ambiguous across books. Signed PF is negative for exported active power with current defined into the converter. If only its magnitude is requested, state the power-flow direction separately.

5.2 Single-phase bridge line-current spectrum

Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark

Assume a full diode or full SCR bridge with constant positive DC current IoI_o, no source inductance and no freewheel interval. With the phase convention of Section 4.1, line current is a square wave delayed by α\alpha. For a diode bridge set α=0\alpha=0.

For a full SCR bridge operating as a line inverter, cos⁡α<0\cos\alpha<0 but sin⁡α>0\sin\alpha>0: it exports active power while still drawing fundamental reactive power. Commutation overlap rounds current transitions and changes both magnitudes and phases; do not apply the zero-overlap spectrum unchanged.

5.3 Semiconverter current spectrum

Past papers · EE 2020–2026 (7 papers): 2 questions, 4 marks

Use constant current IoI_o and the line-current intervals in Section 4.2. The pulse width is π−α\pi-\alpha, centred at (π+α)/2(\pi+\alpha)/2 in the positive half-cycle. That centre, rather than just the first edge, sets the fundamental phase.

5.4 Three-phase line-current spectrum

For the six-pulse full bridge, let va=Vmpsin⁡θv_a=V_{mp}\sin\theta and define α\alpha from natural commutation. At α=0\alpha=0, phase-a line current equals +Io+I_o from π/6\pi/6 to 5π/65\pi/6, equals −Io-I_o from 7π/67\pi/6 to 11π/611\pi/6, and is zero elsewhere. Delayed firing translates this waveform by α\alpha in the ideal no-overlap, constant-current case.

Last-minute recall

  • State the phase-voltage reference before giving harmonic phase.
  • A negative Fourier coefficient adds 180∘180^\circ to a positive-magnitude representation.
  • Source-current harmonics and output-voltage ripple occur at different orders.
  • PF equals distortion factor times displacement factor only for sinusoidal supply voltage.
  • The usual THD-to-distortion relation excludes DC current.
  • Full single-phase bridges give odd current harmonics under constant-current loading.
  • Balanced six-pulse bridges give 6k±16k\pm1 line harmonics.
  • A line-commutated inverter still consumes fundamental reactive power.

Revise offline: the whole Power Electronics handbook as one PDF