Boiling and condensation
Phase change transports latent energy and can produce large heat fluxes for small temperature differences. Identify the phase-change regime before applying a correlation. Surface condition, pressure and fluid properties strongly influence boiling.
6.1 Regimes and latent energy
Boiling creates vapour at a heated surface; condensation forms liquid from vapour at a colder surface. Pool boiling has no imposed bulk flow. Flow boiling combines phase change with externally driven flow. Saturated boiling uses bulk liquid at saturation; subcooled boiling may form bubbles near a wall even when the bulk liquid is colder.
| Pool-boiling regime | What changes as wall superheat increases |
|---|---|
| Natural convection before onset | No sustained bubble production at the wall |
| Nucleate boiling | Bubble activity promotes liquid mixing and high heat transfer |
| Critical heat flux (CHF) | Peak heat flux before widespread vapour blanketing |
| Transition boiling | Increasing dry coverage can reduce heat flux despite higher wall temperature |
| Minimum film-boiling point | Lower end of stable vapour-film operation; associated with the Leidenfrost condition |
| Stable film boiling | Vapour film separates liquid from the wall; heat transfer rises again with temperature |
A schematic boiling curve distinguishes heat-flux maxima from wall-temperature changes.
6.2 Pool-boiling correlations
Use the following expressions for the stated pool-boiling regimes. They do not model a general two-phase flow inside a tube.
6.3 Film condensation on a vertical wall
A wetted wall carries a condensate film whose resistance grows as liquid accumulates downstream. Dropwise condensation exposes more surface directly to vapour and usually gives larger coefficients, but sustained dropwise behaviour depends on the surface.
The exact smooth-film mean/local ratio is ; 0.943 is a rounded coefficient. Assume pure stationary saturated vapour, an isothermal vertical wall, negligible interfacial shear and inertia, a thin smooth laminar film, and conduction across that film. The base expression neglects condensate subcooling. For a plate inclined at angle from the horizontal, replace by when gravity-driven thin-film assumptions still hold; do not extend this to a horizontal plate.
A commonly used subcooling correction replaces inside the coefficient correlation by , where is liquid specific heat (J/(kg K)). This correction modifies the film model; do not silently treat it as the true thermodynamic latent heat in a mass balance.
6.4 Horizontal tubes and tube banks
Condensate drains around a horizontal tube and leaves its underside. In a vertical stack, condensate arriving from upper tubes makes lower films thicker.
Last-minute recall
- Boiling superheat and condensation temperature difference have opposite definitions.
- Latent heat must be in J/kg if the heat rate is in W.
- Nucleate boiling, transition boiling and film boiling need different models.
- CHF marks a maximum heat flux, not a maximum coefficient for every system.
- belongs to a surface–fluid pair.
- Condensate film thickness grows downstream; its local coefficient falls.
- Vertical-film mean coefficient is of its bottom local value.
- Tube-bank drainage lowers the ideal average coefficient as .
- A noncondensable gas invalidates the pure-vapour film-only model.