Chapter 7

Heat exchangers

Use energy balances to relate stream temperatures before applying LMTD or effectiveness. LMTD is convenient when terminal temperatures are known. The effectiveness–NTU method is convenient when inlet conditions and exchanger size are known but outlet temperatures are not.

7.1 Capacity rates and overall resistance

Past papers · ME 2020–2026 (10 papers): 5 questions, 9 marks

Assume steady operation, negligible heat loss to surroundings, negligible axial conduction, and no work. Hot and cold stream heat rates then have equal magnitudes.

For isothermal phase change, use Q˙=m˙pchfg\dot Q=\dot m_{\mathrm{pc}}h_{fg} on that side. Its effective heat-capacity rate tends to infinity; the other stream supplies Cmin⁡C_{\min}. This does not mean its mass flow is infinite.

7.2 LMTD and terminal differences

Past papers · ME 2020–2026 (10 papers): 1 question, 1 mark

The logarithmic mean follows from integrating the local temperature driving force for constant UU and constant single-phase capacity rates (or an isothermal phase-changing stream). Pair temperatures that occur at the same physical end of the exchanger.

Flow arrangementΔT1\Delta T_1ΔT2\Delta T_2
ParallelTh,i−Tc,iT_{h,i}-T_{c,i}Th,o−Tc,oT_{h,o}-T_{c,o}
CounterflowTh,i−Tc,oT_{h,i}-T_{c,o}Th,o−Tc,iT_{h,o}-T_{c,i}

Use a correction factor for multipass or crossflow arrangements: Q˙=UAFΔTlm,counter\dot Q=UA F\Delta T_{\mathrm{lm,counter}}, where dimensionless F≤1F\le1 comes from the applicable arrangement chart or relation. A supplied chart may use its own temperature-ratio definitions; check them before reading FF.

Counterflow terminal differences pair temperatures at the same physical end.Counterflow terminal differences pair temperatures at the same physical end.

7.3 Effectiveness–NTU relations

Past papers · ME 2020–2026 (10 papers): 1 question, 2 marks

Calculate the capacity-rate ratio with the smaller rate in the numerator. The formulas below use an exchanger with constant overall conductance and capacity rates.

7.4 Other arrangements and performance checks

Use the flow arrangement actually shown. “Crossflow” is incomplete unless the mixing condition of each fluid is identified.

Last-minute recall

  • Start with the energy balance on both streams.
  • C=m˙cpC=\dot m c_p is in W/K, not J/K.
  • Maximum duty uses the inlet-to-inlet temperature difference.
  • Pair terminal differences according to physical ends.
  • Equal terminal differences give a finite LMTD by a limit.
  • Isothermal phase change gives Cr=0C_r=0.
  • Use the separate counterflow expression when Cr=1C_r=1.
  • Identify mixing before using a crossflow formula.
  • Fouling increases resistance and reduces UU on the same area basis.