Transformer connections and power sharing
Three-phase banks add a connection-dependent magnitude and phase shift to the winding turns ratio. Resolve winding voltages first, then form line voltages. Parallel units must agree on those terminal phasors.
2.1 Star and delta connections
Past papers · EE 2020–2026 (7 papers): 1 question, 2 marks
Use positive phase sequence . are line magnitudes and are winding-phase magnitudes. The ratio refers to individual HV and LV windings.
| HV–LV connection | HV/LV line-voltage magnitude ratio | Practical point |
|---|---|---|
| Y–Y | Neutral available if brought out; zero-sequence path depends on neutral grounding and core | |
| Δ–Δ | Closed path for triplen magnetising currents; no neutral | |
| Y–Δ | Line-voltage displacement is an odd multiple of 30° | |
| Δ–Y | LV neutral possible; line-voltage displacement is an odd multiple of 30° |
A delta permits triplen harmonic current circulation within its loop; balanced triplen currents cancel in its lines. A grounded star permits zero-sequence line current; an isolated star neutral does not. A tertiary delta can support the required excitation harmonics. The connection name alone does not determine the sign of the phase shift.
2.2 Vector groups from terminal phasors
Past papers · EE 2020–2026 (7 papers): 1 question, 2 marks
Uppercase Y/D/Z describes HV star/delta/zigzag; lowercase y/d/z describes LV. N or n means a brought-out neutral. In clock notation the HV reference is at 12; the hour number locates the LV reference clockwise from it. Compare corresponding line-voltage phasors, or consistently derived phase-to-neutral phasors on both sides.
For an unfamiliar diagram: assign balanced HV phasors; obtain each coil voltage with its marked polarity; divide by turns ratio; join coil ends as drawn; form LV line voltages by subtraction. Never identify a group from a memorised sketch that uses different terminal labels.
2.3 Parallel transformers
Correct polarity, phase sequence and matching phase displacement are essential. Equal no-load secondary voltages prevent circulating current; tap mismatch can be analysed explicitly. Equal per-unit impedance on each unit's own rating, with equal impedance angle, gives proportional kVA sharing.
2.4 Open-delta bank capacity
Two identical single-phase units can supply a balanced three-phase load in open delta. The limitation is the current in each remaining transformer, not an assumed two-thirds bank rating.
Keeping the former closed-delta bank load after removing one transformer makes each remaining unit carry times its rated VA. It is not a continuous permissible condition.
2.5 Autotransformer currents and rating
Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark
In an ideal step-down autotransformer, and . The series portion has turns; the common portion has turns. Input line current is , output line current is . Common-section current opposes the series-section current in ampere-turn effect.
For any reconnection, calculate each physical winding voltage and current first. A small voltage difference gives a large theoretical VA advantage but also a low impedance on the new rating and larger prospective fault current.
Last-minute recall
- Turns ratio is a winding ratio; line ratio includes Y/Δ factors.
- Delta line current is a phasor difference of branch currents.
- Clock 1 is a 30° LV lag; clock 11 is a 30° LV lead.
- Draw winding polarities before naming a vector group.
- Tap mismatch produces no-load circulating current.
- Equal own-base pu impedances give rating-proportional sharing when angles agree.
- Open delta retains 57.735% of the original three-unit rating.
- Autotransformer transferred power has conductive and transformed parts.