Single-phase transformers
A transformer exchanges AC power through mutual flux without changing frequency. Start by choosing the referred side; then keep voltage, current, impedance and rating on that side. The circuit separates excitation current from load current.
1.1 Emf, ratio and polarity
Past papers · EE 2020–2026 (7 papers): 2 questions, 3 marks
are winding turns, is maximum mutual flux (Wb), is frequency (Hz), and is the turns ratio. Voltage references run from dotted to undotted ends. Primary current enters its dot; secondary load current leaves its dot.
With one end of each winding joined, the voltage between the free ends is the phasor sum or difference according to polarity. For in-phase windings, joining like-polarity ends gives ; joining unlike ends gives . Use a reduced test voltage.
A winding linking several core limbs responds to the signed sum of linked fluxes. Sum the relevant flux phasors with the winding senses before multiplying by turns and frequency. Balanced limb fluxes can sum to zero; the drawing determines which fluxes are linked.
1.2 Equivalent circuit and phasor construction
Past papers · EE 2020–2026 (7 papers): 1 question, 2 marks
and are winding resistances and leakage reactances (Ω). The shunt branch represents core-loss resistance and magnetising reactance (Ω), across the mutual-flux emf . Its current is .
To construct a loaded phasor diagram, put on the real axis; place at for lagging load or for leading load. Add parallel to current and 90° ahead of current to obtain . Scale to , add to referred load current, then add primary drops. Flux lags the internal voltage drop by 90° for a lossless magnetising branch.
An original secondary-side lagging-load phasor construction; arrows add head to tail.
For a linear core, use : is mutual-path reluctance (A/Wb), magnetising/leakage inductance (H), and leakage reactance (Ω). Magnetic-circuit evaluation of reluctance and linked flux is an applied prerequisite; see the Electromagnetic Fields and Waves handbook. Do not infer total self-inductance from leakage reactance alone.
1.3 Open-circuit and short-circuit tests
In the OC test one winding is open and the other receives rated voltage at rated frequency. LV excitation is convenient, not mandatory. In the SC test one winding is shorted and the other receives enough reduced voltage to circulate the specified current; HV excitation is usual. Every result belongs to the instrumented side.
1.4 Voltage regulation
Keep primary voltage and frequency fixed. Define regulation using loaded secondary voltage as denominator; some questions instead specify rated voltage. below is the no-load secondary voltage in the approximate referred circuit, is loaded current, and are equivalent series parameters on that side.
For the first-order expression, maximum positive regulation occurs at . Approximate zero regulation on leading load satisfies . For the exact series expression, zero regulation instead requires .
1.5 Efficiency and daily energy
is rated apparent power (VA), is the fraction of rated current at approximately rated voltage, is load power factor, is constant core loss (W), and is rated winding copper loss (W).
1.6 Rating, flux and per-unit quantities
Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark
Heating from copper loss limits current; insulation and core flux constrain voltage and frequency. The kVA rating does not assume a particular load power factor. Reduced voltage does not allow increased winding current unless a new thermal rating is provided.
For core cross-sectional area (m²), ; sinusoidal design requires when winding drop is negligible. is the allowed peak flux density (T); convert mm² to m² using . Rated-current SC voltage in pu equals series impedance magnitude in pu. With a stiff source, approximate short-circuit current at rated voltage is rated current divided by . On a new frequency, reactance scales with frequency; resistance does not simply scale that way. Switching near a supply-voltage zero can produce a large transient flux offset and inrush; residual flux and saturation matter.
Last-minute recall
- Emf uses peak flux and RMS voltage; 4.44 assumes sinusoidal flux.
- Impedance referral uses the square of the turns ratio.
- OC gives the shunt branch; SC gives the series branch.
- Keep OC and SC results on their measured sides until referral.
- Signed load angle makes the regulation formula work for lead and lag.
- Maximum efficiency requires copper loss equal to constant loss.
- All-day efficiency compares energy, including idle energised hours.
- Core flux follows ; winding current still limits kVA.