Synchronous machines
The rotor field locks to the stator rotating field in steady operation. Excitation controls reactive exchange, while mechanical input or shaft load sets real-power transfer. Keep generator current outward and motor current inward when writing phasor equations.
7.1 Construction, electrical angle and winding emf
Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark
Cylindrical rotors have a nearly uniform air gap and are suited to high-speed, few-pole machines. Salient rotors have projecting poles, a nonuniform gap and usually more poles at lower speed. A DC-excited rotor supplies the field; the stator carries the AC armature winding.
Triplen phase emfs cancel in star line voltages; in a closed delta they can drive circulating currents. Chording can eliminate a selected odd harmonic by making . Specify electrical degrees when calculating coil span.
7.2 Cylindrical-rotor phasors
Past papers · EE 2020–2026 (7 papers): 3 questions, 5 marks
is terminal phase voltage. is internal excitation emf; is armature resistance and synchronous reactance per phase (Ω), including leakage and the linearised armature-reaction effect. Use for phase-current magnitude and for the stated current direction.
For a generator with , . Lagging current gives . Leading current can give , or depending on the reactive rise and the current magnitude. For a motor use the minus sign on the cross term. Draw 90° ahead of the current phasor and use the correct addition/subtraction.
Generator and motor phasor constructions with the same lagging terminal current reference; internal emf is found with opposite impedance-drop signs.
The current MMF can also be classified relative to the internal-emf axis. With the relevant outward/inward current convention:
| Current relative to internal emf | Generator armature reaction | Motor armature reaction |
|---|---|---|
| In phase | Cross-magnetising | Cross-magnetising |
| Lags by 90° | Demagnetising | Magnetising |
| Leads by 90° | Magnetising | Demagnetising |
Intermediate angles give both direct and cross components. Familiar classifications by terminal power factor approximate the internal-emf reference; the actual phasor diagram resolves the components when load angle is appreciable.
For a series line between a generator and load, find terminal power factor from and . With a lossless inductive line, but . The generator's is used only when solving for internal emf, not the line's reactive-power drop.
7.3 Power angle and excitation at fixed load
Past papers · EE 2020–2026 (7 papers): 2 questions, 3 marks
Neglect . For a generator define in normal generation. For a motor use in normal motoring. This topic uses positive transfer magnitudes in each operating mode.
At fixed real power and bus voltage, is constant. Increasing excitation on the stable branch reduces load angle and changes reactive exchange. An overexcited generator delivers vars with outward lagging current. An overexcited motor supplies vars while its inward current leads voltage. Underexcitation reverses these reactive signs. The unity-power-factor excitation depends on real load; “normal excitation” is not a universal fixed field current.
7.4 Salient-pole model and slip test
The direct axis follows the rotor pole; the quadrature axis lies between poles. Typically because direct-axis magnetic reluctance is lower. The following generator model neglects and uses . Positive is the demagnetising current component 90° behind , and is in phase with .
7.5 Regulation, OCC, SCC and Potier method
Past papers · EE 2020–2026 (7 papers): 1 question, 2 marks
Measure the open-circuit characteristic (OCC: voltage versus field current) and short-circuit characteristic (SCC: armature current versus field current) at rated speed. The SCC is nearly linear because the resultant air-gap flux is small. The air-gap line is the extension of the initial unsaturated OCC slope.
In the synchronous-impedance (EMF) method find and take its magnitude. It usually overestimates positive regulation because it represents armature reaction as a fixed reactance across saturated operation. A saturated impedance is an operating-point approximation, not a universal machine constant.
To obtain the Potier triangle, plot OCC and rated-current zero-power-factor lagging characteristic on common voltage/field-current axes. From a chosen rated-voltage point on the ZPF curve move horizontally left by the SCC field current for rated armature current. Through that point draw a line parallel to the air-gap line to meet the OCC. Drop a vertical from the intersection onto the original horizontal. The vertical leg is ; the horizontal leg from its foot to the chosen ZPF point is . This separates leakage drop from armature reaction instead of combining both in .
7.6 Synchronisation and parallel operation
Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark
Before closing an alternator onto live busbars, match voltage magnitude, frequency, phase sequence and instantaneous phase. A voltmeter checks magnitude; a synchroscope or properly connected lamp arrangement indicates relative phase and slip frequency. Phase sequence must be checked separately or with an appropriate lamp connection. A wattmeter is useful after connection for load sharing, not as the synchronising phase indicator.
On an infinite bus, voltage and frequency are imposed. Increasing prime-mover input raises real output and load angle. Increasing excitation mainly raises reactive output at fixed real output. For two isolated parallel generators, governor settings share real power and influence frequency; excitation settings share reactive power and influence voltage. Unequal excitation can produce circulating reactive current even at small total real load.
Hunting is rotor oscillation around synchronism after a disturbance. Damper bars develop induced currents during relative motion and damp these oscillations; at ideal balanced synchronous steady state they carry no induced fundamental current. Static stiffness is not by itself a transient-stability guarantee.
7.7 Starting and operation of synchronous motors
Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark
With a fixed-frequency supply and a stationary DC-excited rotor, alternating torque has zero average: a conventional synchronous motor is not self-starting. Damper-cage starting accelerates it as an induction motor; apply DC field near synchronous speed and allow it to pull into step. A suitable field discharge resistance limits induced field voltage during asynchronous starting. An auxiliary motor or a variable-frequency supply offers other starting routes.
Once locked, steady speed is synchronous until pull-out. Increasing shaft load increases motor load angle and required real input. Excess load can break synchronism. Excitation changes power factor while speed remains fixed by supply frequency and pole count.
7.8 Power limits with armature resistance
Past papers · EE 2020–2026 (7 papers): 1 question, 2 marks
When is specified, distinguish armature input/output from converted mechanical power. Let and , with . The following use positive motor/generator load-angle magnitudes as in Section 7.3.
Last-minute recall
- Electrical angle equals pole-pairs times mechanical angle.
- Winding emf uses series turns per phase and both winding factors.
- Generator current leaves; motor current enters.
- Leading generator load does not guarantee negative regulation.
- A fixed-power excitation change alters reactive power and load angle together.
- Saliency adds reluctance power proportional to .
- OCC and SCC ratios use the same field current and phase quantities.
- Synchronisation requires voltage, frequency, sequence and phase agreement.
- Damper bars assist starting and suppress hunting.
- With resistance retained, motor static mechanical limit uses converted power.