Chapter 8

Losses, efficiency and test interpretation

An efficiency calculation is an energy balance with an explicit boundary. Separate winding heat, core loss, rotational loss and external equipment loss. Treat a quantity as constant only under the voltage, frequency, flux, temperature and speed assumptions given.

8.1 Loss classification and temperature

LossModel or causeWhat changes it
Winding copperResistive heating in stator, rotor, armature and field circuitsRMS current squared; winding temperature
Brush contactCurrent times total contact dropArmature current; contact model
Core hysteresisRepeated magnetic cyclingFlux density, frequency and material
Core eddy currentInduced currents within conducting coreFlux density, frequency, lamination thickness and resistivity
Friction and windageBearings, brushes and air dragSpeed and mechanical construction
Stray-loadLeakage-field, additional eddy and nonideal load effectsLoad and machine design; use the specified model

Field copper loss is nearly constant only at fixed field voltage/resistance. Rotor copper loss in an induction motor is not a fixed fraction of total input unless the other losses are neglected. External starting/control resistors belong to drive-system loss; do not silently include them in the machine's internal efficiency.

8.2 Core-loss separation and frequency changes

Past papers · EE 2020–2026 (7 papers): 2 questions, 3 marks

For a fixed core and approximately sinusoidal flux, use a hysteresis model and a classical eddy-current model. Their coefficients absorb material and core-volume factors; the hysteresis exponent is empirical and must be specified for quantitative flux changes.

8.3 Efficiency boundaries and indirect tests

Nameplate kW for a motor normally denotes shaft output; an alternator or transformer kVA rating denotes apparent electrical capacity. Apply the stated power factor to obtain real electrical output. A separately supplied field or exciter must be included or excluded explicitly according to the requested boundary.

For an exact fixed-voltage shunt-motor model with constant rotational loss, no brush drop and no external resistance, use Pin=V(Ia+If)P_{\rm in}=V(I_a+I_f) and Pout=VIa−RaIa2−ProtP_{\rm out}=VI_a-R_aI_a^2-P_{\rm rot}, then differentiate their ratio if an optimum is required. The common “variable loss equals constant loss” shortcut treats line and armature current as approximately equal.

TestPower balance to useMain limitation
Transformer OC/SCOC estimates core loss; SC estimates rated copper loss only at rated currentPredicts efficiency without supplying full output load
Back-to-back transformer testCommon excitation supplies both cores; small injected voltage circulates load current and supplies both winding lossesSeparate supply readings and divide totals only for identical units
DC no-load / Swinburne testNo-load input minus field, armature and brush loss estimates rotational lossAssumes transferable rotational loss; does not reproduce full-load commutation or stray losses
DC regenerative / Hopkinson testMechanically coupled motor–generator returns most power; external net input supplies the combined lossesAccount for all field supplies; dividing loss equally needs justified symmetry
Direct loadingMeasure useful output and every required inputTorque-speed shaft power and electrical power must use the same operating point

For a coupled regenerative pair with no useful external mechanical output, the total power drawn from all external electrical supplies equals the sum of both machines' losses at steady speed. Individual efficiencies need individual copper/field losses and a justified allocation of residual rotational losses.

Last-minute recall

  • Set the efficiency boundary before summing losses.
  • Copper loss uses winding RMS current and resistance at the relevant temperature.
  • A total brush drop is not a per-brush drop.
  • Constant V/fV/f separates hysteresis as ff and classical eddy loss as f2f^2.
  • Rotational loss is not core loss in a stationary transformer.
  • The optimum-loss equality has a specific linear-output/quadratic-loss model.
  • A regenerative test's external input measures combined loss, not either machine's full input.