Losses, efficiency and test interpretation
An efficiency calculation is an energy balance with an explicit boundary. Separate winding heat, core loss, rotational loss and external equipment loss. Treat a quantity as constant only under the voltage, frequency, flux, temperature and speed assumptions given.
8.1 Loss classification and temperature
| Loss | Model or cause | What changes it |
|---|---|---|
| Winding copper | Resistive heating in stator, rotor, armature and field circuits | RMS current squared; winding temperature |
| Brush contact | Current times total contact drop | Armature current; contact model |
| Core hysteresis | Repeated magnetic cycling | Flux density, frequency and material |
| Core eddy current | Induced currents within conducting core | Flux density, frequency, lamination thickness and resistivity |
| Friction and windage | Bearings, brushes and air drag | Speed and mechanical construction |
| Stray-load | Leakage-field, additional eddy and nonideal load effects | Load and machine design; use the specified model |
Field copper loss is nearly constant only at fixed field voltage/resistance. Rotor copper loss in an induction motor is not a fixed fraction of total input unless the other losses are neglected. External starting/control resistors belong to drive-system loss; do not silently include them in the machine's internal efficiency.
8.2 Core-loss separation and frequency changes
Past papers · EE 2020–2026 (7 papers): 2 questions, 3 marks
For a fixed core and approximately sinusoidal flux, use a hysteresis model and a classical eddy-current model. Their coefficients absorb material and core-volume factors; the hysteresis exponent is empirical and must be specified for quantitative flux changes.
8.3 Efficiency boundaries and indirect tests
Nameplate kW for a motor normally denotes shaft output; an alternator or transformer kVA rating denotes apparent electrical capacity. Apply the stated power factor to obtain real electrical output. A separately supplied field or exciter must be included or excluded explicitly according to the requested boundary.
For an exact fixed-voltage shunt-motor model with constant rotational loss, no brush drop and no external resistance, use and , then differentiate their ratio if an optimum is required. The common “variable loss equals constant loss” shortcut treats line and armature current as approximately equal.
| Test | Power balance to use | Main limitation |
|---|---|---|
| Transformer OC/SC | OC estimates core loss; SC estimates rated copper loss only at rated current | Predicts efficiency without supplying full output load |
| Back-to-back transformer test | Common excitation supplies both cores; small injected voltage circulates load current and supplies both winding losses | Separate supply readings and divide totals only for identical units |
| DC no-load / Swinburne test | No-load input minus field, armature and brush loss estimates rotational loss | Assumes transferable rotational loss; does not reproduce full-load commutation or stray losses |
| DC regenerative / Hopkinson test | Mechanically coupled motor–generator returns most power; external net input supplies the combined losses | Account for all field supplies; dividing loss equally needs justified symmetry |
| Direct loading | Measure useful output and every required input | Torque-speed shaft power and electrical power must use the same operating point |
For a coupled regenerative pair with no useful external mechanical output, the total power drawn from all external electrical supplies equals the sum of both machines' losses at steady speed. Individual efficiencies need individual copper/field losses and a justified allocation of residual rotational losses.
Last-minute recall
- Set the efficiency boundary before summing losses.
- Copper loss uses winding RMS current and resistance at the relevant temperature.
- A total brush drop is not a per-brush drop.
- Constant separates hysteresis as and classical eddy loss as .
- Rotational loss is not core loss in a stationary transformer.
- The optimum-loss equality has a specific linear-output/quadratic-loss model.
- A regenerative test's external input measures combined loss, not either machine's full input.