Instrument transformers
Instrument transformers scale high current or voltage to a measurable value and provide isolation. Ratio and phase errors both matter in power measurement. Nominal ratio, turns ratio and actual ratio are different quantities.
6.1 CT and PT connections and burden
Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark
| Property | Current transformer (CT) | Potential transformer (PT/VT) |
|---|---|---|
| Primary connection | In series; carries line current | Across measured voltage |
| Secondary load | Low-impedance current coils and leads | High-impedance voltage coils |
| Dangerous condition | Opening secondary with primary current flowing | Short-circuiting secondary with primary voltage applied |
| Effect of burden | Changes required secondary emf and errors; primary current mainly imposed by line | Changes secondary current and hence primary current and drops |
| Safe unused secondary condition | Short through the specified shorting arrangement | Open, within rated insulation/operating conditions |
6.2 Ratio and phase-error conventions
Use polarity-corrected secondary phasors: is the reversed secondary winding-current phasor aligned with primary current in the ideal CT, and is the secondary voltage aligned with primary voltage in the ideal PT. Prime denotes polarity choice, not referral or differentiation.
6.3 Power and energy through CTs and PTs
The secondary wattmeter sees the difference between the two secondary phase angles. Therefore equal phase shifts cancel, but equal-magnitude shifts in opposite directions add.
Last-minute recall
- CT primary is in series; PT primary is in parallel.
- Never open an energised CT secondary or short an energised PT secondary.
- Burden is VA at specified secondary voltage or current.
- CT turns ratio is secondary/primary; PT is primary/secondary here.
- Actual ratio need not equal either turns ratio or nameplate ratio.
- State polarity correction before defining phase error.
- Phase error becomes especially significant at low power factor.