Beams
A beam needs enough bending and shear resistance, a stable compression flange, and acceptable service deflection. Concentrated reactions also need a local web check. Use the factored bending-moment and shear-force diagrams from analysis; do not assume their maxima occur together.
4.1 Laterally supported bending resistance
Past papers · CE 2020–2026 (14 papers): 1 question, 1 mark
The upper bound limits irreversible deformation under working loads. It is not the lateral-torsional-buckling reduction. A compact section can reach its plastic moment in a strength calculation while the service-yield cap still governs the design value.
Section properties come from the geometry or section table. refers to the extreme fibre on the relevant side; for an unsymmetric section do not use the smaller fibre distance when checking first yield. For plastic section modulus and shape factors, see Structural Analysis.
4.2 Shear resistance and high shear
For a slender web, shear yielding alone is unsafe. Determine shear-buckling resistance before the moment interaction; an ordinary beam may instead be selected with a sufficiently stocky web. Dedicated plate-girder panel and tension-field design is outside this handbook's syllabus scope.
4.3 Lateral-torsional buckling
A beam can move sideways and twist when its compression flange lacks restraint. A vertical support is not necessarily a lateral/torsional restraint. Loading above the shear centre can be destabilising; loading position and end restraint affect the elastic critical moment.
For common fork-supported uniform-moment idealisation, is the distance between lateral/torsional restraints. Between full intermediate lateral restraints, use the segment length; between partial intermediate lateral restraints, the amended code uses 1.2 times the segment length. Other support conditions require the effective-length entry matching lateral, torsional and warping restraint. Do not substitute a column's into a beam's lateral-buckling calculation.
4.4 Concentrated load on a beam web
Check both local bearing/yielding near the flange and buckling of the web strip. They describe different failures. The effective dispersion is truncated by a nearby member end; it cannot spread into steel that is absent.
For a rolled section with flange thickness and root radius , a full one-sided bearing spread is ; an interior load sufficiently far from both ends permits two such spreads. Require the applied load/reaction to pass both checks. Bearing stiffeners carry the excess over local web capacity; load-carrying stiffeners must also pass a compression/buckling check and transfer their forces through their connections.
4.5 Serviceability of beams
Use elastic analysis under the specified serviceability combination and the load category named in the deflection limit. Deflection formulas are in Structural Analysis. The steel design strength cap does not replace a deflection calculation.
| Vertical-deflection situation | Loading for check | Recommended limit |
|---|---|---|
| Industrial simple span, elastic / brittle cladding | Imposed load | / |
| Industrial cantilever, elastic / brittle cladding | Imposed load | / |
| Purlin/girt, elastic / brittle cladding | Imposed or wind load as applicable | / |
| Other-building floor/roof, finishes not susceptible / susceptible to cracking | Imposed load | / |
| Other-building cantilever, finishes not susceptible / susceptible to cracking | Imposed load | / |
is the member span or cantilever projection in the same unit as deflection. IS 800 Table 6 notes that the imposed-load category includes post-construction loads, including superimposed dead load. Apply the serviceability factors from the applicable load combination; use project/question limits when specified.
Last-minute recall
- The compression flange needs lateral restraint, not merely vertical support.
- and are low-shear service-yield caps.
- High shear starts above .
- For a slender web, determine buckling resistance before using shear capacity.
- LTB needs minor-axis inertia, torsion constant and sometimes warping constant.
- Torsion constant is not the polar area moment of an open section.
- Check web bearing and web buckling under concentrated loads.
- Deflection uses the specified service load and cladding/finish category.