Chapter 10

Balanced three-phase circuitsEE

Use a single-phase equivalent only after confirming balanced sources and equal phase loads. A balanced three-wire system has zero neutral current, but line and phase quantities depend on whether the load is star or delta.

10.1 Phase sequence and line quantitiesEE

Past papers · EE 2020–2026 (7 papers): 2 questions, 4 marks

For positive sequence abcabc, take Van=Vph∠0∘V_{an}=V_{\mathrm{ph}}\angle0^\circ, Vbn=Vph∠−120∘V_{bn}=V_{\mathrm{ph}}\angle-120^\circ and Vcn=Vph∠120∘V_{cn}=V_{\mathrm{ph}}\angle120^\circ. Here nn is source neutral and all phasors are RMS.

If a question gives unequal phase loads, apply KCL directly instead of using balanced line-current shortcuts. For a floating star point n′n' fed from known phase voltages, the one-node equation is ∑k=a,b,c(Vkn−Vn′n)/Zk=0\sum_{k=a,b,c}(V_{kn}-V_{n'n})/Z_k=0. This is Section 2.2 applied to three source nodes, not a new balanced-load identity.

10.2 Three-phase power and compensationEE

Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark

Let ϕ\phi be the impedance angle of one balanced phase. Use line-to-line voltage and line-current magnitudes in the 3\sqrt3 formulas, with the load phase angle.

For parallel balanced loads, add their complex powers first. Then Iline=∣Stotal∣/(3Vline)I_{\mathrm{line}}=|S_{\mathrm{total}}|/(\sqrt3V_{\mathrm{line}}). For a balanced star with per-line source impedance, analyse one phase including that line impedance before calculating the load phase voltage.

10.3 Two-wattmeter readingsEE

Take current coils in lines a,ca,c, voltage coils measuring Vab,VcbV_{ab},V_{cb}, and positive current into the load. Let Wa=ℜ(VabIa∗)W_a=\Re(V_{ab}I_a^*) and Wc=ℜ(VcbIc∗)W_c=\Re(V_{cb}I_c^*); these wiring definitions fix the signs.

Last-minute recall

  • Star phase voltage is line voltage divided by 3\sqrt3.
  • Delta line current is phase-current magnitude times 3\sqrt3.
  • Phase sequence controls the signs of the 30∘30^\circ shifts.
  • The angle in three-phase power is the load phase impedance angle.
  • Add parallel-load complex powers before finding line current.
  • A delta bank needs one-third the per-phase capacitance of a star bank for equal total vars and line voltage.
  • Keep negative wattmeter readings signed.