Isolated footings
Size the plan using service-load soil pressure, then design the concrete for factored structural actions. Bending, one-way shear, punching, bearing and anchorage are distinct checks; passing one does not establish the others.
8.1 Plan area and contact pressure
Full contact requires every corner pressure nonnegative: . For uniaxial eccentricity this is the middle-third rule. Soil is not assumed to resist tension.
8.2 Flexure and one-way shear
Take a concentric rectangular column with dimensions on a footing . The cantilever projections from the column faces are and . Bending is checked at the column face, not its centre.
Use the singly reinforced rectangular design equations across the full section width (or consistently per metre). For varying contact pressure, integrate pressure over the exterior cantilever: force is its area, and moment is its first moment about the column face. For a sloping footing, use actual depth and width at the critical section; do not insert edge thickness as the column-face effective depth.
8.3 Punching shear
Equivalently, for , : only reaction outside the critical perimeter causes punching. An edge/corner column, opening, clipped perimeter or unbalanced moment needs its actual critical perimeter and nonuniform shear distribution. Do not use the interior concentric formula unchanged. The same basic critical-perimeter principle applies at slab–column connections in flat slabs.
Distinct critical sections for a concentric footing: face for flexure, d for one-way shear and d/2 perimeter for punching.
8.4 Column bearing, dowels and footing reinforcement
Dowel diameter must not exceed column-bar diameter by more than 3 mm. Develop bars/dowels into both column and footing for the forces they transfer. Check development length at the bending-critical face and at abrupt section changes; bends may be needed when the projection is short.
For footings on soil, edge thickness is at least 150 mm and nominal cover at least 50 mm. Minimum reinforcement and spacing follow solid-slab rules. For concrete sections thicker than 1 m, also provide nominal reinforcement of 360 mm/m in each direction on each face; this does not replace the required minimum tensile reinforcement based on depth. Top reinforcement is needed wherever analysis produces top tension; a uniformly loaded concentric cantilever footing normally has bottom tension.
Last-minute recall
- Size plan area against allowable service soil pressure.
- Structural footing design uses factored net upward actions.
- Full contact requires nonnegative pressure at every corner.
- Flexure at column face; one-way shear at ; punching at .
- Punching force excludes the upward reaction inside the critical perimeter.
- Bearing-area enhancement is capped at two and limited by geometry.
- Rectangular-footing short-direction steel is concentrated in a central band.
- Check anchorage and cover after choosing bars and depth.