Cables, electric stress and insulators
Cable questions depend on radial electric-field variation. Insulator-string questions are capacitive-divider networks: the disc nearest the conductor usually carries the largest voltage in the simple tower-capacitance model.
3.1 Single-core cable
Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark
Use a coaxial cable with conductor radius , sheath inner radius , length , and uniform dielectric permittivity . Neglect end effects. is conductor-to-sheath voltage, not line-to-line voltage.
At fixed and , the conductor radius minimising maximum stress is . Thus . This is an electrical-stress optimum, not a total-cost or thermal optimum.
Longer cable means larger capacitance and lower insulation resistance. For sections joined end to end with continuous core and earthed sheath, conductor resistances add in series while insulation leakage conductances add in parallel (neglect conductor voltage drop). For a three-core cable model with equal core-to-sheath capacitance and equal pairwise core capacitance , balanced per-phase effective capacitance is .
3.2 Grading the cable insulation
Capacitance grading uses several dielectric layers. Intersheath grading fixes intermediate metallic sheath potentials. The target is a lower peak field, not a uniform field within each homogeneous layer.
Equal peak stress in capacitance grading requires to be equal. Place higher permittivity nearer the conductor. For intersheaths with a common allowed maximum stress, allocate proportional to .
3.3 Suspension strings
Let each disc have series capacitance and each intermediate metal junction have shunt capacitance to the earthed tower. Ignore junction-to-line capacitance in this model. Number discs from tower to conductor.
For , each disc carries and efficiency is 100%. A grading ring changes the electrostatic network; do not apply the unmodified three-disc formula after adding ring capacitances. Longer cross-arms reduce tower coupling; capacitance grading and guard rings can improve voltage sharing.
Intermediate shunt capacitances distort the voltage sharing of a three-disc string.
3.4 Surface field and corona
High surface electric stress ionises surrounding air. Larger effective conductor radius and smoother surfaces reduce local stress; bundles also reduce inductive reactance. Weather and surface condition matter, so do not infer a numerical corona onset from voltage alone.
For general overhead geometry, solve the potential-coefficient matrix for conductor charges and then obtain the fields. Empirical weather-dependent corona-loss constants are not universal SI constants.
Last-minute recall
- Cable voltage is core to sheath.
- Maximum radial stress occurs at the conductor surface.
- At fixed outer radius, the stress optimum has .
- Cable capacitance grows with length; insulation resistance falls.
- A larger dielectric permittivity is useful near the core in graded insulation.
- Count insulator discs from the tower before using a voltage ratio.
- String efficiency uses the most stressed disc, not the average disc voltage.