Chapter 3

Cables, electric stress and insulators

Cable questions depend on radial electric-field variation. Insulator-string questions are capacitive-divider networks: the disc nearest the conductor usually carries the largest voltage in the simple tower-capacitance model.

3.1 Single-core cable

Past papers · EE 2020–2026 (7 papers): 1 question, 1 mark

Use a coaxial cable with conductor radius aa, sheath inner radius bb, length ℓ\ell, and uniform dielectric permittivity ε=ε0εr\varepsilon=\varepsilon_0\varepsilon_r. Neglect end effects. VV is conductor-to-sheath voltage, not line-to-line voltage.

At fixed bb and VV, the conductor radius minimising maximum stress is a=b/ea=b/e. Thus b/a=eb/a=e. This is an electrical-stress optimum, not a total-cost or thermal optimum.

Longer cable means larger capacitance and lower insulation resistance. For sections joined end to end with continuous core and earthed sheath, conductor resistances add in series while insulation leakage conductances add in parallel (neglect conductor voltage drop). For a three-core cable model with equal core-to-sheath capacitance CsC_s and equal pairwise core capacitance CmC_m, balanced per-phase effective capacitance is Cs+3CmC_s+3C_m.

3.2 Grading the cable insulation

Capacitance grading uses several dielectric layers. Intersheath grading fixes intermediate metallic sheath potentials. The target is a lower peak field, not a uniform field within each homogeneous layer.

Equal peak stress in capacitance grading requires εiri\varepsilon_i r_i to be equal. Place higher permittivity nearer the conductor. For intersheaths with a common allowed maximum stress, allocate ΔVi\Delta V_i proportional to riln⁡(ri+1/ri)r_i\ln(r_{i+1}/r_i).

3.3 Suspension strings

Let each disc have series capacitance CC and each intermediate metal junction have shunt capacitance kCkC to the earthed tower. Ignore junction-to-line capacitance in this model. Number discs from tower to conductor.

For k=0k=0, each disc carries V/nV/n and efficiency is 100%. A grading ring changes the electrostatic network; do not apply the unmodified three-disc formula after adding ring capacitances. Longer cross-arms reduce tower coupling; capacitance grading and guard rings can improve voltage sharing.

Intermediate shunt capacitances distort the voltage sharing of a three-disc string.Intermediate shunt capacitances distort the voltage sharing of a three-disc string.

3.4 Surface field and corona

High surface electric stress ionises surrounding air. Larger effective conductor radius and smoother surfaces reduce local stress; bundles also reduce inductive reactance. Weather and surface condition matter, so do not infer a numerical corona onset from voltage alone.

For general overhead geometry, solve the potential-coefficient matrix for conductor charges and then obtain the fields. Empirical weather-dependent corona-loss constants are not universal SI constants.

Last-minute recall

  • Cable voltage is core to sheath.
  • Maximum radial stress occurs at the conductor surface.
  • At fixed outer radius, the stress optimum has b/a=eb/a=e.
  • Cable capacitance grows with length; insulation resistance falls.
  • A larger dielectric permittivity is useful near the core in graded insulation.
  • Count insulator discs from the tower before using a voltage ratio.
  • String efficiency uses the most stressed disc, not the average disc voltage.