Bases, generation and transmission choices
A consistent base and current direction prevent most factor-of-three errors. Generation questions combine energy accounting with operating constraints; transmission questions compare how voltage, current and losses change.
1.1 Three-phase power and sign conventions
Write the complex power at the terminal where the voltage is measured. In a load calculation, current enters the load. In a load-flow calculation, current leaves the bus and enters the network.
For a balanced star, and ; for a balanced delta, and . These magnitude relations do not include the 30° phasor shift.
1.2 Per-unit conversion
Choose a common three-phase power base. Propagate line-voltage bases through transformers using rated line-voltage ratios; the ideal transformer ratio then disappears from the per-unit network.
With these bases, for the positive-sequence per-phase circuit: no factor of three. Percentage impedance divided by 100 gives per-unit impedance on its stated rating.
1.3 Generating sources and energy conversion
Steam and gas turbines convert thermal energy into shaft power. Hydro turbines use water head. Nuclear plants supply heat to a thermal cycle. Photovoltaic plants convert irradiation directly into DC electricity; wind turbines extract part of the airflow power. Converter interfaces control their connection to the AC grid.
Hydro head must be net of hydraulic losses. Wind power scales as only while and efficiency are held fixed and rated-power limiting is absent. Use the efficiencies and physical constants supplied in the question. .
1.4 Load curve and plant utilisation
A chronological load curve preserves time order. A load-duration curve sorts demands from highest to lowest; its area gives the same energy but cannot identify when a peak occurred.
Plant-use factor uses only the hours the plant operates in its denominator. Diversity is at least one when the group and individual maxima refer to the same observation interval. Capacity factor and utilisation factor are not interchangeable.
1.5 AC and DC transmission
AC transformers make voltage conversion simple. HVAC needs reactive-power management and synchronism between connected AC systems. HVDC provides controlled real-power transfer between asynchronous systems and avoids steady capacitive charging current in the DC cable. Converters add cost, losses and control requirements; no universal break-even distance applies.
Line-commutated converters require an AC voltage for commutation and absorb reactive power. Voltage-source converters can control real and reactive power within their ratings. A bipolar link with poles at has .
Last-minute recall
- Use three-phase MVA with line-to-line kV for the impedance base.
- The same physical impedance must survive a base conversion.
- Per-unit complex power has no extra factor of three.
- A load-duration curve preserves energy, not chronology.
- Hydro uses net head; installed capacity is not average output.
- Compare AC and DC only after specifying voltage and conductor assumptions.